{"MatterId":13713,"MatterGuid":"0F497D1F-B2A6-410D-8CB1-8125285419AE","MatterLastModifiedUtc":"2026-06-10T14:22:18.367","MatterRowVersion":"AAAAAADAciQ=","MatterFile":"15-10464","MatterName":null,"MatterTitle":"FIRE-033-2026 A - G\r\nProperty Address:\r\n1251 Providence Boulevard, Suite 101, Deltona, FL 32725\r\nParcel ID: 8132-01-01-0050\r\nProperty Owner: \r\nObsidian ML 8 LLC.\r\n11995 EL Camino Real\r\nSan Diego, CA 92130-2539\r\n\r\nViolation: A\r\nCity of Deltona Ordinance,Chapter 42, Article IV, Fire Codes, Ch. 42-186. – Adopted. Florida Fire Prevention Code 8th Edition, NFPA 1, CH. 11.1.7.3.1 – Each disconnecting means shall be legibly marked to indicate its purpose unless located and arranged so the purpose is evident. In other than one- or two-family dwellings, the marking shall include the identification of the circuit source that supplies the disconnecting means. The marking shall be of sufficient durability to withstand the environment involved. [70:110.22(A)] \r\n\r\nCorrective Action:\r\nPlease label each disconnecting means (breakers) to indicate its function on the panel schedule. [1:11.1.7.3.1] \r\n\r\nViolation: B\r\nCity of Deltona Ordinance, Chapter 42, Article IV, Fire Codes, Ch. 42-186. – Adopted. Florida Fire Prevention Code 8th Edition, NFPA 1, CH. 11.1.4.2 – The re locatable power taps shall be directly connected to a permanently installed receptacle. \r\n\r\nCorrective Action:\r\nPlease plug each power strip directly into a receptacle and not into another power strip. Power strip cords shall not exceed 6 ft. in length. \r\n\r\nViolation:C\r\nCity of Deltona Ordinance, Chapter 42, Article IV, Fire Codes, Ch. 42-186. – Adopted. Florida Fire Prevention Code 8th Edition, NFPA 1, CH. 11.1.3.2 – Multi Plug adapters shall not be used as a substitute for permanent wiring or receptacles.\r\n\r\nCorrective Action:\r\nPlease discontinue use of the power strips. \r\n\r\nViolation:D\r\nCity of Deltona Ordinance, Chapter 42, Article IV, Fire Codes, Ch. 42-186. – Adopted. Florida Fire Prevention Code 8th Edition, NFPA 101, CH 7.10.2.1 – A sign complying with 7.10.3, with a directional indicator showing the direction of travel, shall be placed in every location where the direction of travel to reach the nearest exit is not apparent.\r\n\r\nCorrective Action:\r\nPlease provide approved covers for the directional arrows on the illuminated exit sign. \r\n\r\nViolation:E\r\nCity of Deltona Ordinance, Chapter 42, Article IV, Fire Codes, Ch. 42-186. – Adopted. Florida Fire Prevention Code 8th Edition NFPA 1, CH 13.6.1.1 – The selection, installation, inspection, maintenance, recharging, and testing of portable fire extinguishers shall be in accordance with NFPA 10 and Section 13.6. \r\n\r\nCorrective Action:\r\nFire extinguisher shall be inspected/tested annually by a licensed fire extinguisher company. Please contact your fire extinguisher service provider to schedule this inspection. \r\n\r\nViolation:F\r\nCity of Deltona Ordinance, Chapter 42, Article IV, Fire Codes, Ch. 42-186. – Adopted. Florida Fire Prevention Code 8th Edition, NFPA 1, CH. 1.7.12.10 – No construction work shall proceed until the AHJ has reviewed the plans for compliance with the applicable permits have been issued.\r\n\r\nCorrective Action:\r\nObtain an issued permit for the installation of the new electrical panel. Please contact your fire extinguisher service provider to schedule this inspection.\r\n\r\nViolation:G\r\nCity of Deltona Ordinance, Chapter 42, Article IV, Fire Codes, Ch. 42-186. – Adopted. Florida Fire Prevention Code 8th Edition, NFPA 101, CH. 7.9.2.1 – Emergency illumination shall be provided for a minimum of 1 ½ hours in the event of failure of normal lighting. \r\n\r\nCorrective Action:\r\nPlease repair the non-functional emergency light. \r\n\r\nFire Safety Inspector Lisa Nadeau","MatterTypeId":70,"MatterTypeName":"Code Violation","MatterStatusId":63,"MatterStatusName":"New Business","MatterBodyId":187,"MatterBodyName":"Special Magistrate","MatterIntroDate":"2026-06-04T00:00:00","MatterAgendaDate":"2026-06-24T00:00:00","MatterPassedDate":null,"MatterEnactmentDate":null,"MatterEnactmentNumber":null,"MatterRequester":null,"MatterNotes":null,"MatterVersion":"1","MatterCost":null,"MatterText1":null,"MatterText2":"jcotterman@deltonafl.gov","MatterText3":null,"MatterText4":null,"MatterText5":null,"MatterDate1":null,"MatterDate2":null,"MatterEXText1":null,"MatterEXText2":null,"MatterEXText3":null,"MatterEXText4":null,"MatterEXText5":null,"MatterEXText6":null,"MatterEXText7":null,"MatterEXText8":null,"MatterEXText9":null,"MatterEXText10":null,"MatterEXText11":null,"MatterEXDate1":null,"MatterEXDate2":null,"MatterEXDate3":null,"MatterEXDate4":null,"MatterEXDate5":null,"MatterEXDate6":null,"MatterEXDate7":null,"MatterEXDate8":null,"MatterEXDate9":null,"MatterEXDate10":null,"MatterAgiloftId":0,"MatterReference":null,"MatterRestrictViewViaWeb":false,"MatterReports":[]}