{"MatterId":13584,"MatterGuid":"3B3505A0-BBB8-4E22-84D9-C19D9AD6C1F8","MatterLastModifiedUtc":"2026-04-07T14:23:52.35","MatterRowVersion":"AAAAAAC915U=","MatterFile":"15-10358","MatterName":null,"MatterTitle":"FIRE-004-2026 Massey\r\nProperty Address:\r\n111 Howland Boulevard, Deltona, FL 32738\r\nParcel ID: 9206-04-00-0040\r\nProperty Owner: \r\nFairwinds Credit Union\r\n3087 N. Alafaya Trail\r\nOrlando, FL 32826\r\n\r\nViolation: A\r\nCity of Deltona Ordinance, Chapter 42, Article IV, Fire Codes, Ch. 42-186. – Adopted Florida Fire Prevention Code 8th Edition, NFPA 1, 13.1.6 – Fire Protection System Test and Maintenance Paperwork Required – Detailed records documenting all systems and equipment testing and maintenance shall be kept by the property owner and shall be made available upon request for review by the AHJ.\r\n\r\nCorrective action: \r\nPlease provide a copy of the current fire alarm inspection/maintenance report and current backflow inspection/maintenance report and current fire sprinkler inspection/maintenance report. \r\n\r\nViolation: B\r\nCity of Deltona Ordinance, Chapter 42, Article IV, Fire Codes, Ch. 42-186. – Adopted Florida Fire Prevention Code 8th Edition, NFPA 1, 13.1.8 – Fire Protection System Not in Operating Condition – All fire protection systems and devices shall be maintained in a reliable operating condition and shall be replaced or repaired where defective or recalled. \r\n\r\nCorrective action: \r\nFire sprinkler system is red tagged indicating deficiencies to the system. Please contact your fire sprinkler service provider to have all deficiencies corrected.\r\n\r\nViolation: C\r\nCity of Deltona Ordinance, Chapter 42, Article IV, Fire Codes, Ch. 42-186. – Adopted Florida Fire Prevention Code 8th Edition, NFPA 1, 13.1.9 – Fire Sprinkler Impairments/Deficiencies Not Repaired – Whenever impairments, critical deficiencies, or non-critical deficiencies are identified in water-based fire protection systems maintained in accordance with NFPA 25, they shall be corrected in a time frame approved by the AHJ.\r\n\r\nCorrective action: \r\nBackflow system is red tagged, indicating deficiencies to the system. Please contact your fire sprinkler service provider to have all deficiencies corrected.\r\n\r\nViolation: D\r\nCity of Deltona Ordinance, Chapter 42, Article IV, Fire Codes, Ch. 42-186. – Adopted Florida Fire Prevention Code 8th Edition, NFPA 1, 13.1.1 – Permit Required – Fire Protection System – The AHJ shall have the authority to require that construction documents for all fire protection systems be submitted for review and approval, and a permit issued prior to installation, rehabilitation, or modification. \r\n\r\nCorrective action: \r\nObtain a permit for the removal of the fire alarm cellular communicator and newly installed fire alarm control panel. \r\n\r\nFire Safety Inspector Lisa Nadeau","MatterTypeId":70,"MatterTypeName":"Code Violation","MatterStatusId":86,"MatterStatusName":"Old Business","MatterBodyId":187,"MatterBodyName":"Special Magistrate","MatterIntroDate":"2026-04-07T00:00:00","MatterAgendaDate":"2026-04-22T00:00:00","MatterPassedDate":null,"MatterEnactmentDate":null,"MatterEnactmentNumber":null,"MatterRequester":null,"MatterNotes":null,"MatterVersion":"1","MatterCost":null,"MatterText1":null,"MatterText2":"jcotterman@deltonafl.gov","MatterText3":null,"MatterText4":null,"MatterText5":null,"MatterDate1":null,"MatterDate2":null,"MatterEXText1":null,"MatterEXText2":null,"MatterEXText3":null,"MatterEXText4":null,"MatterEXText5":null,"MatterEXText6":null,"MatterEXText7":null,"MatterEXText8":null,"MatterEXText9":null,"MatterEXText10":null,"MatterEXText11":null,"MatterEXDate1":null,"MatterEXDate2":null,"MatterEXDate3":null,"MatterEXDate4":null,"MatterEXDate5":null,"MatterEXDate6":null,"MatterEXDate7":null,"MatterEXDate8":null,"MatterEXDate9":null,"MatterEXDate10":null,"MatterAgiloftId":0,"MatterReference":null,"MatterRestrictViewViaWeb":false,"MatterReports":[]}