{"MatterId":13530,"MatterGuid":"0535FBCC-E62F-44DC-A759-D8B5E27623B6","MatterLastModifiedUtc":"2026-03-10T18:37:01.53","MatterRowVersion":"AAAAAAC8LJA=","MatterFile":"15-10313","MatterName":null,"MatterTitle":"FIRE-044-2025   Massey\r\nProperty Address:\r\n679 Vicksburg Street, Deltona, FL 32725\r\nParcel ID: 8130-04-38-0350\r\nProperty Owner: \r\nCesar Borges\r\nTamara Pita Pinheiro\r\n679 Vicksburg Street\r\nDeltona, FL 32725\r\n\r\nViolation  A: \r\nCity of Deltona Ordinance, Chapter 42, Article IV, Fire Codes, Ch. 42-186. – Adopted Florida Fire Prevention Code 8th Edition, NFPA 1, CH. 1.12.8- The AHJ shall be authorized to require permits for conditions listed in 1.7.12.2, 1.7.12.5, and 1.7.12.6, unless otherwise permitted by 1.7.12.9. \r\n\r\nCorrective action: \r\nObtain an issued permit for the change of occupancy classification (shed to apartment building) or restore space to original condition.  \r\n\r\nViolation  B: \r\nCity of Deltona Ordinance, Chapter 42, Article IV, Fire Codes, Ch. 42-186. – Adopted Florida Fire Prevention Code 8th Edition, NFPA 101, CH. 30.3.5.1 – All buildings shall be protected throughout by an approved, suppressive automatic sprinkler system installed in accordance with 30.3.5.1 through 30.3.5.6. \r\n\r\nCorrective action: \r\nInstall a supervised automatic fire sprinkler system throughout the structure. Installation shall be done with issued permit by City of Deltona and be conducted by a licensed fire sprinkler contractor.\r\n\r\nViolation  C: \r\nCity of Deltona Ordinance, Chapter 42, Article IV, Fire Codes, Ch. 42-186. – Adopted Florida Fire Prevention Code 8th Edition, NFPA 1, CH. 18.2.3.2.1- A fire apparatus access road shall be extended to within 50 ft (15m) of at least one exterior door that can be opened from the outside and the provided access to the interior of the building. \r\n\r\nCorrective action: \r\nProvide an approved fire department access road to the new apartment building, extending within 50 ft of at least one exterior door that provides access to the interior of the building. Fire department access roads shall have an unobstructed road with not less than 24 ft, and an unobstructed vertical clearance of not less than 17 ft, stabilized and capable of supporting a 32-ton emergency vehicle. \r\n\r\nCaptain / Assistant Fire Marshal Samuel Schaller","MatterTypeId":70,"MatterTypeName":"Code Violation","MatterStatusId":86,"MatterStatusName":"Old Business","MatterBodyId":187,"MatterBodyName":"Special Magistrate","MatterIntroDate":"2026-03-10T00:00:00","MatterAgendaDate":"2026-03-25T00:00:00","MatterPassedDate":null,"MatterEnactmentDate":null,"MatterEnactmentNumber":null,"MatterRequester":null,"MatterNotes":null,"MatterVersion":"1","MatterCost":null,"MatterText1":null,"MatterText2":"jcotterman@deltonafl.gov","MatterText3":null,"MatterText4":null,"MatterText5":null,"MatterDate1":null,"MatterDate2":null,"MatterEXText1":null,"MatterEXText2":null,"MatterEXText3":null,"MatterEXText4":null,"MatterEXText5":null,"MatterEXText6":null,"MatterEXText7":null,"MatterEXText8":null,"MatterEXText9":null,"MatterEXText10":null,"MatterEXText11":null,"MatterEXDate1":null,"MatterEXDate2":null,"MatterEXDate3":null,"MatterEXDate4":null,"MatterEXDate5":null,"MatterEXDate6":null,"MatterEXDate7":null,"MatterEXDate8":null,"MatterEXDate9":null,"MatterEXDate10":null,"MatterAgiloftId":0,"MatterReference":null,"MatterRestrictViewViaWeb":false,"MatterReports":[]}